Position : Home > Product > YOKOGAWA > Pressure Transmitters

EJA310A Absolute Pressure Transmitter
  • EJA310A Absolute Pressure Transmitter

EJA310A Absolute Pressure Transmitter

Details

EJA310A Absolute Pressure Transmitter

The high performance absolute pressure transmitter model EJA310A can be used to measure liquid, gas, or steam pressure. It outputs a 4 to 20 mA DC signal corresponding to the measured absolute pressure.
The EJA Series is available with BRAIN, HART, FOUNDATION™ fieldbus or PROFIBUS PA communication protocols.
 
Downloads for EJA310A
 
Features

Excellent performance and stability

The EJA series uses a silicon resonant sensor formed from monocrystal silicon, a perfect material which has no hysteresis in pressure or temperature changes. The sensor minimizes overpressure, temperature change, and static pressure effects, and thus offers unmatched long-term stability.
Compact and light-weight design
Half the weight of conventional models thanks to miniaturization of the casing with the amplifier ASIC, pressure cell structure, and flange. The ASIC uses the minimum number of parts and improves the reliability of the amplifier.
Fieldbus communication capability
Fieldbus is a digital two-way communication system. It is a revolutionary technology for configuring instrumentation control systems and a promising successor to the standard 4 to 20 mA analog communication used in most field instruments today.EJA series offers two types of fieldbus models, FOUNDATION™ fieldbus Low Voltage Mode and PROFIBUS PA devices, which ensure interoperability between Yokogawa and other manufactures. As for software, the EJA series incorporates two AI function blocks that compute differential and static pressures to allow flexible configuration of instrumentation.
 
Specifications
 

 

EJA310A Absolute Pressure Transmitter

L Capsule

M Capsule

A Capsule

Range

0 to 10 kPa abs

0 to 130 kPa abs

0 to 3 MPa

(0 to 2.95 inHg abs)

(0 to 38 inHg abs)

(0 to 430psia)

Span

0.67 to 10 kPa

1.3 to 130 kPa

0.03 to 3 MPa

(0.2 to 2.95 inHg)

(0.38 to 38 inHg)

(4.3 to 430 psi)

Accuracy

±0.2%

±0.15%

±0.15%

Degrees of protection

IP67, NEMA 4X, and JIS C0920 immersion proof

Certificates

FM, CENELEC ATEX, CSA, IECEx

Output

4 to 20 mA DC or FOUNDATION™ fieldbus or PROFIBUS PA 2-wire system with digital communication

Supply voltage

BRAIN and HART:10.5 to 42 V DC (10.5 to 30 V DC for Intrinsically safe type)

Fieldbus:9 to 32 V DC (9 to 24 V DC for Entity model and 9 to 17.5 V DC for FISCO model)

Ambient temperature

-40 to 85 deg C (-40 to 185 deg F) (general use type)

-30 to 80 deg C (-22 to 176 deg F) (with integral indicator)

Process temperature

-40 to 120 deg C (-40 to 248 deg F) (general use type) for M and A capsule

-40 to 100 deg C (-40 to 212 deg F) (general use type) for L capsule

Maximum overpressure

500 kPa abs

500 kPa abs

4.5 MPa abs

(72psia)

(72psia)

(645psia)

Mounting

2-inch pipe mounting

Wetted parts material

Capsule

SUS316L (Diaphragm material is Hastelloy C-276)

Cover flange

SUS316

Housing

Cast

 

分享到:
Hits:  UpdateTime:1022  【Printing】  【Close